Partial-fill cavity wall, Kooltherm K106

Brick, a 90 mm phenolic board held against the inner leaf with a clear residual cavity, blockwork and plaster.

U ≈ 0.17 W/m²Kindicative, wall ·355 mmtotal

Layers, outside to inside

LayerThicknessW/(m·K)R
Brick (generic) 102 mm λ 0.77 0.13
Air cavity (unventilated) (generic) 50 mm R 0.18 fixed 0.18
Kingspan Kooltherm K106 90 mm λD 0.019 4.74
Aerated concrete block (generic) 100 mm λ 0.16 0.63
Plaster (gypsum) (generic) 13 mm λ 0.51 0.03

Where this fits

Where a full fill is unwanted — exposed sites, or a specification that insists on a clear cavity — a rigid phenolic board gets the same performance from less thickness than mineral wool, at a higher price per square metre. The residual cavity must stay genuinely clear and the boards must be tight to the inner leaf; a gap behind the board lets air loop around the insulation and quietly undoes it. K106's declared 0.019 W/(m·K) is the lowest conductivity in this catalogue.

What the calculation assumes

Series calculation through continuous layers, with the residual cavity taken as an unventilated airspace at a fixed resistance. Ties and board joints are not modelled. Surface resistances are the EN ISO 6946 defaults for this element. This is an indicative figure for comparing constructions, not a compliance calculation.

Sources

Change it, or use it

Open it in the calculator to swap a layer, change a thickness or solve for a target U-value — the result keeps its own URL, so a build-up you have altered is still something you can send to someone. Or take this one straight into the editor, where it arrives as a named wall type you can assign to the walls you have drawn: the thickness follows and the U-value comes with it. Nothing is assigned until you say so.